Product Overview
GF-DPCV-01 is a brass differential pressure control valve with threaded connections. A sensing capillary and an internal diaphragm regulating mechanism adjust the valve opening automatically, holding the differential pressure across the controlled circuit within the set range.
The valve is intended for building heating, chilled water and variable-flow water systems, on circuits that require a stable branch differential pressure. It suits systems in which terminal control valves open, close or modulate frequently.
In variable-flow systems the network differential pressure moves as terminal loads change, which can lead to uneven flow distribution, unstable control valve operation and pipework noise. GF-DPCV-H-B-T responds automatically to changes in differential pressure, limiting the effect of network pressure fluctuation on the controlled branch and giving terminal control valves a steadier working condition, which improves hydraulic balance and operating stability.
| Parameter | Value |
|---|---|
| Nominal Diameter | DN 15-50 |
| Nominal Pressure(PN) | PN 20 |
| Hydrostatic shell test pressure | 30 bar |
| Differential pressure over the valve | 20-250 kPa |
| Shut-off function | Not provided |
| Working Temperature | -10 ...+120°C |
| Storage and transport temperature | -40~+70°C |